Whittling away at watts

Reducing head loss in hydronic systems reduces the kilowatt-hours of electrical energy required for operation.

RENEWABLE HEATING DESIGN || By John Siegenthaler, P.E.

RENEWABLE HEATING DESIGN
|| By John Siegenthaler, P.E.

RENEWABLE HEATING DESIGN || By John Siegenthaler, P.E.

electronic circuit

[vchal/[iStock/Getty Images Plus] via Getty Images.

When designing hydronic circuits, most of us focus on what’s necessary for that circuit to absorb thermal energy at a heat source, carry it along like a conveyor belt and release that energy at one or more heat emitters. After all, that’s the principal objective of any hydronic heating system — regulating thermal energy transfer from source to load.

However, thermal energy isn’t the only energy being processed in hydronic systems. Electrical energy is being converted into mechanical energy. The latter is what’s referred to as “head” in the hydronics industry. Circulators convert electrical energy into head energy.

The efficiency of that conversion can vary over a wide range, from single digits to upwards of 60%. Small wet rotor circulators operating near either end of their pump curve have very low electrical to head energy conversion efficiency, in most case less than 10%. Larger circulators with more efficient multi-horsepower motors applied so they operate near the middle of their pump curve represent the higher end of the efficiency range.

Head energy is eventually dissipated into heat due to friction between fluid molecules, as well as friction between the fluid and surfaces it flows across.

Every hydronic heating professional understands there’s a cost associated with operating a circulator. Every kilowatt-hour of electrical energy “fed” to the circulator’s motor comes at a price. In some areas of the U.S., it’s only a few cents. In other locations, such as remote villages in Alaska where diesel fuel is trucked in to power generators, it’s over half a dollar per kilowatt-hour.

It’s not hard to understand that reducing head loss in hydronic systems reduces the kilowatt-hours of electrical energy required to operate them. But do we really think about this enough as we design?

Head converted to dollars

Imagine a closed hydronic circuit constructed of type M copper tubing and having an equivalent length of 200 feet. Assume this circuit needs to convey a flow rate of 6 gpm along a round trip between a mechanical room and the coil of an air handler. What tube size would you normally select for this circuit?

The usual sizing criteria for copper tubing in smaller hydronic systems is to keep the flow velocity no higher than 4 feet per second. That flow velocity corresponds to a flow rate of 6.4 gpm in 3/4-inch type M copper tubing, so, 3/4-inch is likely the common size selected to handle this flow requirement. My guess is many of you didn’t have to consult a flow velocity versus flow rate chart in order to select a 3/4-inch tube for this flow rate. You just knew from previous experience that a 1/2-inch tube was too small and a 1-inch tube was probably not necessary for 6 gpm, so you picked the size in between.

Let’s work in a few simple calculations to see if that was a good choice.

Assuming the 200 foot by 3/4-inch copper tube circuit was carrying water at an average temperature of 120° F, it would have the circuit head loss curve shown in Figure 1.

PME Feb 2021 Fig 1

Figure 1

ENLARGE

You can make a circuit head loss curve like this by graphing head loss versus flow rate values that can be looked up in many design references. The data in these references is usually listed as feet of head loss per 100 feet of pipe. Since our assumed circuit has an equivalent length of 200 feet, we can just double the head loss values, plot the points on the graph and draw a smooth curve through them.

Figure 2 shows the same head loss curve along with the pump curve of a typical small wet rotor “zone” circulator. The point where these two curve cross is called the operating point. It’s where the mechanical energy, referred to as “head” supplied to the water by the circulator, exactly matches the head energy being dissipated from the water by friction. If you draw a line straight down from the operating point, you can find the flow rate for system operation. In this case, it's about 5.9 gpm. Since this flow rate is very close to the target flow rate of 6 gpm, this circulator would be an acceptable selection.

PME Feb 2021 Fig 2

Figure 2

ENLARGE

Figure 3 shows the same curves as Figure 2, but adds another curve (shown in green) representing the “wire-to-water efficiency” of the circulator (e.g., the efficiency at which the circulator converts electrical energy into head energy). The efficiency values are shown a decimal percentages on the graph’s right vertical axis.

PME Feb 2021 Fig 3

Figure 3

ENLARGE

At the operating point of 5.9 gpm, the circulator has a wire-to-water efficiency of 19.5%. That value is not very impressive, but it also not far below the peak wire-to-water efficiency of this circulator, which is about 22%.

Input > Output

The owner of a hydronic system doesn’t pay, at least directly, for head energy. They pay for the electrical energy needed to operate the circulator that imparts head energy to the water. You can estimate that cost by considering the power demand of the circulator, and the total on-time of the circulator.

The electrical power input to a circulator can be estimated using Formula 1:

Equation 1 1

Where:
wₑ = electrical power required by circulator (watts)
f = flow rate in circuit (gpm)
H = head loss of circuit while operating at flow rate (f) (feet of head)
D = density of fluid circulating in system (lb/ft³)
n = wire-to-water efficiency of circulator operating at flow (f) and head (H) (decimal %)

For the operating point shown in Figure 3, the estimated electrical input to the circulator would be estimated at:

Equation 2 1

The annual operating cost of any device that requires a specific power input and operates for a known number of hours can be easily calculated using Formula 2.

Equation 3 1

Where:
Cannual = annual operating cost ($/yr)
t = number of hours pump is on per year (hours/yr)
P = input power to circulator (watts)
$/kwhr = cost of electricity (dollar / kilowatt-hour)

If the circulator represented in Figure 3 operated for 3,000 hours per year, in a location where electricity costs $0.15 / kWh, its annual operating cost would be:

Equation 4 1

Consider the options

How would this operating cost change if the circuit was constructed of 1 inch copper tubing rather than 3/4-inch copper tubing? I’m sure most of you know it would go down, but by how much, and is the reduction worth considering? Back to the math for some answers.

The head loss curve for a circuit constructed of 1-inch type M copper tubing, and having an equivalent length of 200 feet, is shown (in red) in Figure 4.

PME Feb 2021 Fig 4

Figure 4

ENLARGE

If the same circulator, operating at the same speed setting, was used in this circuit, the flow rate would increase to about 10.2 gpm (as shown by the yellow square at the new operating point in Figure 4). But remember, the target flow rate was 6 gpm. We don’t need to operate the circuit at higher flow rates. So, the designer now looks for a different circulator, or looks at how the pump curve would change if the currently selected circulator could operate at a lower speed.

Assume the circulator’s speed could be reduced so that its new pump curve is the brown curve in Figure 4. The intersection between the circuit head loss curve for the 200 feet by 1-inch Type M copper circuit and the new pump curve occurs at a flow rate of about 6.2 gpm. This is again close enough to the target flow rate to be an acceptable option.

The head loss at the operating point shown by the yellow triangle in Figure 4 is now about 4.5 feet. Assuming the circulator’s wire-to-water efficiency remains essentially the same at the reduced speed, the electrical input to the circulator is now estimated as:

Equation 5

The annual operating cost of the circulator under the same conditions as previously assumed (3,000 hours per year and $0.15 / kWh) would now be $12.02.

The 1-inch tubing combined with operating the circulator at lower speed produces about the same flow rate using 60% less electrical energy.

Although a 60% reduction in energy use should get anyone’s attention, you may still think that the difference in operating cost of $18.22 per year is trivial. However, little differences add up over time. If we assumed the cost of electrical energy increased at 3% per year, and totaled this difference in operating cost over a 20 year period, the total operating cost savings for using 1 inch rather than 3/4 inch tubing would be:

Equation 6

Obviously it costs more to construct the circuit using 1-inch rather than 3/4-inch tubing, and this added cost would have to be deducted from the lifecycle saving associated with lower operating cost. Still, it’s likely that the “net” savings in operating cost would exceed the added installation cost within 20 years, and perhaps much sooner in areas where electricity is more expensive.

Be vigilant

If your goal is to maximize the technical advantages of hydronic versus air-based heat delivery, you should always be looking for ways to reduce the pumping power requirements of your systems.

Consider the head loss characteristics of the heat sources, heat emitters, dirt separators, mixing valves, heat exchangers and other components you select. The lower they are, the lower the potential operating cost of the system. Don’t “settle” on high head loss components if there are competitive options available with lower head loss.

Transition your designs to what soon will be the “new normal” of higher efficiency circulators with electronically commutated motors.

The automotive and aerospace industries have been working for decades to reduce the drag of vehicles they produce. Lower drag results in high fuel efficiency, and both of these industries have achieved major advances in fuel efficiency compared to 40 years ago.

The hydronic equivalent of this is would be designing components and circuits with lower head loss. If you’re a manufacturer, don’t take a dismissive attitude that installers will simply have to use larger circulators to accommodate the head loss requirements of your hardware, and thus it’s not “your problem.”

For example, some mod/con boilers require dedicated circulators that draw over 200 watts. The sole function of that circulator is to move flow through the boiler at an acceptable rate. Separate circulators are required for the distribution system.

Several decades ago, there was no need for dedicated boiler circulators in single boiler systems. The head loss of a cast iron sectional boiler was low enough that the distribution circulators could easily move flow through the entire system.

That’s still the case for cast-iron boilers, as well as some contemporary hydronic heat sources where low head loss was an integral part of the design objectives. In other cases, it appears that hydraulic efficiency has been willingly sacrificed for gains in thermal efficiency, reduced materials or smaller size.

Such tradeoffs aren’t limited to boilers. Some water-to-refrigerant heat exchangers used in geothermal heat pumps also have a voracious appetite for head energy. Combine this with long earth loop circuits with minimal pipe sizes, and the low wire-to-water efficiency of small wet rotor circulators with PSC motors, and you may need upwards of 1,000 watts of circulator input power just to move heat from the ground to a residential sized geothermal heat pump. The unimpressive hydraulic power requirement of geothermal heat pump systems is seldom discussed. Instead the geo-narrative focusses on impressive values of thermal efficiency such as coefficient of performance (COP) and energy efficiency ratio (EER). In the end, the owner of that heat pump system doesn’t pay for COP or EER. They pay for kilowatt-hours, whether they go to the compressor, the earth loop circulator(s) or other electrically operated hardware in the system.

As you design hydronic system and align your design philosophy with modern imperatives such as decarbonization, remember that head energy is a terrible thing to waste.

John Siegenthaler, P.E., is principal of Appropriate Designs, in Holland Patent, New York, and author of  “Modern Hydronic Heating.” He can be reached at john@hydronicpros.com.